Lifting station calculator: work out discharge flow and head
Your lifting station must deliver at least
With faeces and without a cutter, an inner diameter of at least 80 mm is required.
Below 0.7 m/s solids can settle. Choose a smaller diameter if permitted.
Above 2.3 m/s it gets noisy and pressure loss rises. Choose a larger diameter.
That is beyond our standard filters. Contact us for a suitable lifting station.
How we calculate
Discharge units (DU) per EN 12056-2, system I; wastewater flow = K × √ΣDU. Pressure pipe per EN 12056-4: velocity 0.7 – 2.3 m/s, with faeces and no cutter at least DN 80. Total head = height difference + pipe friction (Hazen-Williams) + minor losses from bends, non-return valve and gate valve. A guideline – have the final design checked by an installer.